25.11.2026

warpva

Powering The Digital Era

Opto-coupled three-phase AC power fault detection

Opto-coupled three-phase AC power fault detection

Nikola Tesla’s brainchild is monitored opto-digitally in this revisit of an earlier “magnetic” Design Idea.

My interest was piqued by a recent clever Design Idea from one of my favorite contributors, Jayapal Ramalingam. While looking into duplicating RJ’s design, however, I ran into difficulties trying to source the “star-connected three-phase transformer” illustrated in his Figure 1.


Figure 1 Today’s Design Idea provides an implementation alternative to this earlier published three-phase transformer-based approach.

It seems that such small, specialized magnetics are neither widely carried by familiar distributors nor inexpensive even when available. Of course, three separate single phase transformers, with one dedicated to each phase, might alternatively work. But while perhaps  easier to source, that idea wasn’t very appealing to me, either. It didn’t really offer better economy and certainly wouldn’t be very compact.

Southchip Showcases Automotive Power, Charging, and Load-Control Solutions at electronica Munich

11.25.2026

From AI Platforms to Industry Innovation: How NVIDIA Connects Startups to Build an AI Ecosystem

11.25.2026

NSING Featured CRA, AI Robotics, Motor Control and Digital Energy at electronica 2026

11.24.2026

Wow the engineering world with your unique design: Design Ideas Submission Guide

So I decided to try a different, non-magnetic, and significantly simpler approach. Figure 2 shows the result.


Figure 2 An opto-isolator is assigned to each AC phase to monitor both connection and sequence integrity. R1, R2, R3 resistance = 1000 Vinrms ohms, power rating = Vin/1000 watts.

Here’s how it works.

As RJ explains in his Design Idea, it’s essential that all three power phases:

  • Criterion 1: be present and properly energized and
  • Criterion 2: be correctly connected to their respective sequence terminals.

Failure to satisfy criterion #1 (a condition called “single phasing”) is likely to create damaging overheating. Meanwhile, violating #2 by mis-connecting (mis-seqencing) the phase connections is likely to make the connected motor run in reverse. The resulting likelihood of damage to driven equipment is obvious. Figure 3’s sketch of three-phase graphics helps explain how Figure 2’s circuitry detects these fault conditions.


Figure 3 Note, in these characteristic voltage waveforms of three-phase AC power, that if all three phases are present (criterion #1 listed earlier), the summed positive voltage is always greater than zero. If phasing is also correct (criterion #2), phase B is positive at the phase A positive-going zero crossing.

If any phase power voltage is missing (i.e., criterion #1 is violated), then at least one of U2’s pins 3, 4, or 5 will sit at a constant +5v. Consequently U2’s output pin 6 will periodically go to zero, turning on Q4, discharging C2, and holding U2 pin 2 low. This combination of conditions will drive pin 8 high. That level is then inverted by U2 pin 10, generating a low status output and flagging the error condition.

If all phase signals are present and correct, then once every AC mains cycle period (16.7ms if the mains frequency is 60Hz, 20.0ms if 50Hz), the phase A signal is applied to regenerative (Schmitt) trigger U1 pin 4. There it becomes a clean clock trigger signal at U1 pin 11. This results in U1 pin 12 capturing a sample of the complement of the phase B signal at the moment of the phase A positive zero crossing.

If the result is zero, then criterion #2 is violated, and U2 pin 10 will go to zero, flagging a not-OK status.  If it’s one, on the other hand, we’re then good to go!

Thanks, Nikola! Or wait…was three-phase actually Mikhail Dolivo-Dobrovolsky’s idea?

Stephen Woodward’s relationship with EDN’s Design Ideas column goes back quite a long way. Over 200 submissions have been accepted since his first contribution back in 1974.  They have included best Design Idea of the year in 1974 and 2001.